Open Access
Issue
Renew. Energy Environ. Sustain.
Volume 1, 2016
Article Number 15
Number of page(s) 5
DOI https://doi.org/10.1051/rees/2016012
Published online 10 June 2016

© M. Adouane et al., published by EDP Sciences, 2016

Licence Creative CommonsThis is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

1 Introduction

The lack of an electrical network in remote areas and the prohibitively high connection cost of grid extension and rough topography often lead to exploration of other options. Today, the diesel generator is the most used for decentralized electrification [1]. Nevertheless, the fuel supply costs are very high and gradually increase with distance.

Algeria has recently launched a major program in renewable energy [2]; we had to find a way to replace the generators that are used in our desert regions. Ghardaïa (32°26′ N 03°46′ E) with an annual average solar radiation estimated to 4.98 kWh/m2/day [3,4] is blessed with renewable energy resources which can be properly utilized for electricity generation. Thus reduce not only the dependence of electricity generation on conventional fuel but also the emissions of greenhouse gases.

The hybrid systems photovoltaic/generators offer a real advantage for decentralized rural electrification. They assure savings in costs [5] compared to single source of energy solutions. The design of hybrid systems and their technical and economic optimization [69] is significantly more complex, it requires a precise analysis of multiple parameters and factors that can influence the performance and competitiveness of the system. Several search works has been carried out on hybrid systems with respect the performance, optimization and other parameters of importance.

The present study investigates the possibility of using a stand-alone photovoltaic/LPG (liquid petroleum gas) generator hybrid power system for low-cost electricity production to satisfy the energy load requirements of a remote and isolated area in Algeria. In this context, the dimensions of the hybrid system are determined according to the availability of the photovoltaic energy resources and the load energy requirements. Thereafter economic performance of the system is compared with that of other supply options such as diesel generation.

2 Demand analysis

The proposed hybrid system is supposed to supply a domestic load. Households in rural areas of Ghardaïa [4] are simple and do not require large amounts of electrical energy for lighting, cooking and entertaining. The determination of the load is one of the most important steps in the design of hybrid energy systems. In this study, a hypothetical home model of a family composed of seven (07) members is considered.

To consume the least amount of energy and reduce the size of the photovoltaic system, we choose the low consumption equipment. These loads are based primarily on: the energy saving lamps (5 fluorescent light bulbs, 23 W each), 2 fans (usually ceiling fan, 60 W each) and a television (TV, 60 W). The electricity requirement for lighting is not the same, with an increase during winter due to timing of sunset and sunrise. Fans are used only in summer, normally at night, with an operating time estimated 4 h/day. Average TV operating time is 5 h per day. The primary load or energy consumption pattern usually varies over 24 h and over different months of the year. Figure 1 shows two load profiles on a day of summer (April–October) and winter (November–March).

We can see that the demand for electricity varies throughout the day. In the morning (6:00 to 8:00) and lunch (11:00 to 13:00), family members are at home for breakfast, lunch and rest, an increases electricity demand is observed. The maximum demand occurs at night (17:00 to 21:00) where a large part of equipments are connected.

thumbnail Fig. 1

Load profile on winter (November–March) and summer (April–October).

3 Solar energy potential

Algeria experiences some of the highest levels of solar radiation in the world, the average daily solar radiation varies between 4.5 kWh/m and 6.5 kWh/m. The annual averages of irradiance are available from the Institute. The meteorological data (irradiance and temperature) in the entire year of 2013 was measured at the Unit of Applied Research in Renewable Energies (URAER) that is located in Ghardaïa city. As shown in Figure 2.

The solar radiation data for the selected remote area was estimated to range between 2.35 kWh/m2/day and 6.86 kWh/m2/day with an average annual solar radiation estimated to 4.98 kWh/m2/day. It can be noticed that more solar irradiance can be expected from the month of May to August while less solar irradiance is to be expected from November to February.

The average temperature is a variable climate with a significant impact on the behavior of equipment. The analysis of this data is crucial. It is observed in Figure 2, winter temperatures range between 7 °C and 21 °C. They climb to 35 °C in May to reach an average of 40 °C in July and August. Mercury can rise up to 45 °C and beyond during heat waves.

thumbnail Fig. 2

Variations of irradiance and temperature.

4 Hybrid renewable system configuration

The economic study is performed on the HOMER software; it allows us to compare the financial and technical constraints on the use of two different types of generators technologies (Diesel and LPG) on the operating costs. We present in Figure 3 the relative diagram HOMER program adopted for the hybrid system.

The autonomous hybrid PV/generator power system considered is a combination of PV array, generator and battery bank, DC/AC inverter, controller and other accessory devices and cables. According to such a block diagram, PV array, battery bank and DC load are all connected through an intermediate DC bus, the last in turn connected to the AC load through a DC/AC inverter and distribution network.

The PV array work to satisfy the DC load and AC load demands. When the output power of the PV array, which depends on the solar radiation variations, is abundant, the generated power, after satisfying the load demand, will be supplied to feed the battery bank until it is fully charged. On the contrary, during the nights or days with low sunlight, the output power is poor; the battery bank will release power to assist the hybrid system to meet the load requirements until the battery bank is depleted then the generator starts.

thumbnail Fig. 3

Configuration of hybrid PV/generator system in HOMER software.

5 System description and components

The various components of hybrid photovoltaic system are introduced into the HOMER software with technological availability options, component cost and availability of resources. The technical and economic parameters of the various components of the hybrid system adopted are shown in Table 1.

The cost of generator depends on its size and the fuel used. The generator fuel is modeled by a linear curve which is characterized by a slope and an intercept coefficient. In this study two different generators are considered, diesel and gas butane. The default slop and intercept coefficients are 0.234 l/h/kW and 0.244 l/h/kW respectively for the Diesel generator, 0.108 kg/h/kW and 0.124 kg/h/kW respectively for the butane gas generator. Table 1 represents different cost parameters of generators.

Table 1

Technical parameters and cost of components.

6 Results and discussions

Energy balance calculations are performed for each configuration of the considered hybrid photovoltaic system. The configurations obtained are selected according to their feasibility, the cost of installation. The profitability of the operation is evaluated on the life of the project, estimated a priori to 25 years. The calculations of the cost of hybrid system take into account costs such as capital and interest, depreciation, operating costs, maintenance and fuel. HOMER produced results that we can show as possible configurations list sorted by cost lifecycle (net present cost NPC). It also displays simulation results in tables and graphs. We show in Figure 4 the results obtained for a photovoltaic hybrid system with two types of generator:

  • configuration -1-: Hybrid system with a diesel generator;

  • configuration -2-: Hybrid system with a LPG generator.

In analyzing the different points in Figure 4, we find that:

  • in configuration -1-, the hybrid system, which combines photovoltaics with a diesel generator, is favored over other combinations, because of the low cost per kWh produced which is estimated at $0.474;

  • in configuration -2-, the hybrid system, which combines the generator gases with batteries is favored over other combinations, because of the low cost per kWh produced which is estimated at $0.348 (4). Despite its high initial cost estimated at $8730, it favors the hybrid system combining solar with a gas generator; because it reduces the operation time of the generator 710 h, so it saves fuel and reduces pollution;

  • the initial investment cost is $9030 for diesel configuration, whereas it is $8730 for the LPG configuration, which is due to the acquisition price of different types of generator, with $1450 for the diesel generator against $1150 for the LPG generator;

  • for the same period of operation of 884 h (6); diesel generator consumes 1,397 liters of fuel, whereas the generator gases consumes 680 kg of gas (5), which directly influences the cost of operating the system with $885/year for the configuration -1- and $627/year for configuration -2- with a spread of $258/year (2). This results in a cost of electricity produced $0.474/kWh for the first configuration against $0.396/kWh for the second (4); and

  • the total cost of the system (3) is higher in the configuration -1- with a total cost of $18,474 against $15,442 for the configuration -2- in economy carry a $3,032 (3) throughout the operation system.

thumbnail Fig. 4

Impact of generator technology on costs.

7 Technical and environmental analysis of the system

For each of these possible solutions, HOMER provides all the operating parameters of the components and the entire system (the total energy produced, proportion of renewable energy and emissions of air pollutants...).

7.1 Electric power generation

Energy production over a year is detailed in Table 2.

Production systems involving the following fractions described in the table and that show significant participation of the photovoltaic source that reaches 42%.

Table 2

Annual energy produced.

7.2 Distribution of installation costs

The evaluation of the total project cost for the three configurations considered is shown in Figure 5.

The diesel generator has the highest cost (about double that of the photovoltaic or gas generator and three times that of batteries), this is due to high fuel prices and maintenance costs.

thumbnail Fig. 5

Breakdown of costs of the installation.

7.3 Environmental analysis

The environmental analysis of the hybrid system HOMER assesses emissions of air pollutants. Table 3 summarizes the total emission of pollutants in the three cases examined configurations.

From this table, it is possible to significantly reduce emissions of pollutants by the integration of a generator run on butane gas. According to the results, the emissions of pollutants can be reduced by approximately 50% compared to the use of a diesel generator in the hybrid system, especially emissions of CO2 and CO responsible for the greenhouse effect.

Table 3

Emission of air pollutants.

8 Conclusion

In this paper, a study relating to the design of a hybrid energy system on the scale of a house has been developed. This study takes place in four main steps, evaluation of energy demand and solar resource, evaluating energy options and the selection of the system.

Through this study, an assessment of the impact of the technology of generator and the change in the inclination angle of photovoltaic modules on production and energy savings of a hybrid energy system in the region Ghardaïa was performed. It was found that a considerable fuel savings can be carried out in photovoltaic hybrid systems with using a backup generator running on butane gas. For those areas where the price of fuel increases progressively with isolation, fuel economy is fundamental.

The results of this study can be used as reference for deployment of stand-alone photovoltaic hybrid systems to supply cost effective electricity to customers while protecting the environment in remote rural areas where solar resources are available.

References

  1. S. Anjali, C. Patrick, T. Daniel, B. Martin, Accès à l’électricité en Afrique subsaharienne : retours d’expérience et approches innovantes ( Agence française de développement, 2012) [Google Scholar]
  2. A.B. Stambouli, Algerian renewable energy assessment: the challenge of sustainability, Energy Policy 39, 4507 (2011) [CrossRef] [Google Scholar]
  3. http://www.mem-algeria.org/fr/enr/pot.htm [Google Scholar]
  4. M. Adouane, M. Haddadi, K. Touafek, S. AitCheikh, Monitoring and smart management for hybrid plants (photovoltaic-generator) in Ghardaïa, J. Renew. Sustain. Energy 6, 023112 (2014). DOI:10.1063/1.4871095 [CrossRef] [Google Scholar]
  5. H.G. Beyer, T. Degner, Assessing the maximum fuel savings obtainable in simple wind diesel systems, Sol. Energy 61, 5 (1997) [CrossRef] [Google Scholar]
  6. S. Rehman, M. Mahbub Alam, J.P. Meyer, L.M. Al-Hadhrami, Feasibility study of a wind–pv–diesel hybrid power system for a village, Renew. Energy 38, 258 (2012) [CrossRef] [Google Scholar]
  7. J. Andrews, B Shabani, Dimensionless analysis of the global techno-economic feasibility of solar-hydrogen systems for constant year-round power supply, Int. J. Hydrog. Energy 37, 6 (2012) [CrossRef] [Google Scholar]
  8. A. Kaabeche, M. Belhamel, R. Ibtiouen, Techno-economic valuation and optimization of integrated photovoltaic/wind energy conversion system, Sol. Energy 85, 2407 (2011) [Google Scholar]
  9. A. Chaurey, T.C. Kandpal, A techno-economic comparison of rural electrification based on solar home systems and PV microgrids, Energy Policy 38, 3118 (2010) [CrossRef] [Google Scholar]

Cite this article as: Mabrouk Adouane, Ismail Tabet, Daoud Rezzak, Khaled Touafek, Sitayeb Abdelkader, Houam Yahia, Feasibility study of a hybrid plants (photovoltaic–LPG generator) system for rural electrification, Renew. Energy Environ. Sustain. 1, 15 (2016)

All Tables

Table 1

Technical parameters and cost of components.

Table 2

Annual energy produced.

Table 3

Emission of air pollutants.

All Figures

thumbnail Fig. 1

Load profile on winter (November–March) and summer (April–October).

In the text
thumbnail Fig. 2

Variations of irradiance and temperature.

In the text
thumbnail Fig. 3

Configuration of hybrid PV/generator system in HOMER software.

In the text
thumbnail Fig. 4

Impact of generator technology on costs.

In the text
thumbnail Fig. 5

Breakdown of costs of the installation.

In the text